Specifications:
Current rating range: 40~80A
Input voltage rating: 125/250VAC
Interrupting Capacity: 125/250VAC x 1,000A(UL 1077)
Typical life: 500 operations at 200% overload
Insulation co-ordination: Rated impulse withstand voltage 2.5kV
Dielectric Strength: >1,500VAC/min
Insulation Resistance: >100MOHM (DC 500V)
Degree of protection: operating area IP40
Mechanical/Environmental Data
Operating Ambient Temperature: -10 to +60℃℃
Termination: Thickness 1.5mm; 10/24 unc Screwa
Nickle of platedNickle of plated
Mounting: Various options. See Ordering Information and drawings
Compliance with Rohs
The product accords with the requirement of ROHS( 2011/65/EU) Contacts use Exempted item of RoHS Directive 2010/571/EU 8(a)
Compliance with REACH, PAHS, PH1, PH2, PH3
Typical applications
Tarnsforms, Motors, Battery chargers, Power supplies
appliances, extra low voltage systems, machinery.
Calibration(at25)
100% of Rated Current: Hold , No Trip
150% of Rated Current: Trip Within 1 Hour
200% of Rated Current: 5-38 sec Trip
300% of Rated Current: 3.0-7.5 sec Trip