Technical data
Current rating range: 3-16A
Input voltage rating: 125 / 250VAC : 50VDC.
Interrupting Capacity: 125 / 250VAC X 1 , 000A ( UL 1077 ).
Typical life: 1,000 operations at 200% overload.
Insulation co-ordination: Rated impulse withstand voltage 2 . 5kv.
Dielectric Strength: 1500VAC / min.
Insulation Resistance: > 100MOHM ( DC 500V.
Degree of protection : Terminal area IP00 , operating area IP40.
Mechanical/Environmental Data
Operating Ambient Temperature:-10℃to+60℃.
Termination: 250(6. 35mm) quick connects or solder terminals.
Mounting Various options. See Ordering Information and drawings
Typical applications
Tarnsforms, Motors, Battery chargers, Power suppliesappllances, extra low voltage systems, machinery.
Calibration(at25℃)
100% of Rated Current: Hold, No Trip
135% of Rated Current: Trip Within 1 Hour
.200% of Rated Current: 5.2-30. sec Trip
300% of Rated Current: 1.5-5.5 sec Triip
Approval
Approval File No Rated current Rated voltage
ULUL E155159 3-16A 125/250VAC.50VDC
TUV SUD B150158611006 3-16A 125/250VAC.
CCC 3-16A 125/250VAC.
VDE 3-16A 125/250VAC